Siemens 7SC80 Manual page 159

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
1819
51c-1 ANSI Cur.
1820
51c-1 Rec. Cur.
1821
51c-1 MinO.T
1825A
51c Time adder
1901
50Nc-2 PICKUP
1902
50Nc-2 DELAY
1903
50Nc-1 PICKUP
1904
50Nc-1 DELAY
1905
51Nc PICKUP
1906
51Nc T-DIAL
1906
51Nc T-DIAL
1907
51Nc T-DIAL
1908
50Nc-3 PICKUP
1909
50Nc-3 DELAY
1910
51Nc Drop-out
1911
51Nc IEC
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
0.00 .. 30.00 sec
0.00 .. 30.00 sec
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.01 .. 20.00 sec; ∞
0.50 .. 15.00 ; ∞
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
Disk Emulation
Instantaneous
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
2.4 Dynamic Cold Load Pickup
Default Setting
Comments
NO
51c-1 ANSI Curve
NO
51c-1 Recloser Curve
0.01 sec
Min Operating Time 51c-1
0.00 sec
Constant time adder 51c
7.00 A
50Nc-2 Pickup
35.00 A
0.00 sec
50Nc-2 Time Delay
1.50 A
50Nc-1 Pickup
7.50 A
0.30 sec
50Nc-1 Time Delay
1.00 A
51Nc Pickup
5.00 A
0.50 sec
51Nc Time Dial
0.50 sec
51Nc Time Dial
5.00
51Nc Time Dial
∞ A
50Nc-3 Pickup
∞ A
0.00 sec
50Nc-3 Time Delay
Disk Emulation
Drop-out Characteristic
Normal Inverse
IEC Curve
Functions
159