Functions
2.29 Recloser Setting Summary
Special Parameters in
Easy Setting GUI View
Delayed Curve y Gnd
Min Operating Time
Delayed Curve y Ph
Enable Direction.
Delayed Curve y Gnd
Enable Direction.
Delayed Curve y Phase
Directional
Delayed Curve y
Ground Directional
Loss of Load Diversity
Enable Cold Load
Pickup Phase
Restore Minimum Trips
Minimum Trip CLP
Curve x Phase
420
C
Setting Options
0.00 .. 30.00 sec
YES
NO
YES
NO
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
0 .. 21 600 sec
OFF
ON
1 .. 600 sec; ∞
1 A
0.10 .. 4.00 A; ∞
5 A
0.50 .. 20.00 A; ∞
Default Setting Description
0.01 sec
Set the minimum oper-
ating time for the
Delayed curve y
ground.
YES
This setting will determine
if the Delayed curve y
phase would enable
direction judgement.
YES
This setting will determine
if the Delayed curve y
ground would enable
direction judgement.
Forward
This setting will determine
that the Delayed curve
y phase would pickup in
forward, reverse direction
or no-direction required.
Forward
This setting will determine
that the Delayed curve
y ground would pickup
in forward, reverse direc-
tion or no-direction
required.
3600 sec
This setting will determine
the Loss of Load
Diversity time.
OFF
This setting will determine
if the Cold Load
Pickup Phase would be
enabled.
600 sec
This setting will determine
restore the time of
Restore Minimum
Trips.
1.00 A
Set the minimum trip
values for the CLP curve
5.00 A
x phase.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017