Siemens 7SC80 Manual page 662

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
2251
47NPS-1 Pickup
2252A 47NPS-1 D.Ratio
2253
47NPS-1 Delay
2254
47NPS-2 Pickup
2255A 47NPS-2 D.Ratio
2256
47NPS-2 Delay
2300
59N DT
2301
59N IT
2302
Disp.Volt. from
2310
59N DT-1 Pickup
2311A 59N DT-1 DO
2312
59N DT-1 Delay
2313
59N DT-2 Pickup
2314A 59N DT-2 DO
2315
59N DT-2 Delay
2320
59N IT Pickup
2321
59N IT D.Ratio
2322
59N IT TD
2323
59N IT T Res.
2325A 67N-TOC T adder
2701
50 1Ph
2703
50 1Ph-2 PICKUP
2704
50 1Ph-2 DELAY
2706
50 1Ph-1 PICKUP
2707
50 1Ph-1 DELAY
2800
Capacitor Test
2801
Cap.holdup time
2802
CapTestInterval
662
Function
C
Setting Options
47NPS Over-
2 .. 240 V
volt.
47NPS Over-
0.90 .. 0.99
volt.
47NPS Over-
0.00 .. 100.00 sec;
volt.
47NPS Over-
2 .. 240 V
volt.
47NPS Over-
0.90 .. 0.99
volt.
47NPS Over-
0.00 .. 100.00 sec;
volt.
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
Measured Vx
Measured VGnd
Calculated 3V0
27/59 O/U Volt.
1.0 .. 100.0 V; ∞
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
0.00 .. 3600.00 sec;
27/59 O/U Volt.
1.0 .. 100.0 V; ∞
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
0.00 .. 3600.00 sec;
27/59 O/U Volt.
1.0 .. 100.0 V
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
0.1 .. 140.0 ; ∞
27/59 O/U Volt.
0.00 .. 60.00 sec
67 Direct. O/C
0.00 .. 30.00 sec
50 1Ph
OFF
ON
50 1Ph
1A
0.001 .. 1.600 A; ∞ 0.300 A
5A
0.005 .. 8.000 A; ∞ 1.500 A
50 1Ph
0.00 .. 60.00 sec; ∞ 0.10 sec
50 1Ph
1A
0.001 .. 1.600 A; ∞ 0.100 A
5A
0.005 .. 8.000 A; ∞ 0.500 A
50 1Ph
0.00 .. 60.00 sec; ∞ 0.50 sec
Recl. Cap. Test
OFF
ON
Recl. Cap. Test
0.1 .. 10.0 sec
Recl. Cap. Test
12 .. 672 hour
Default Setting
Comments
30 V
47NPS-1 Pickup
0.95
47NPS-1 Drop out Ratio
0.50 sec
47NPS-1 Time Delay
50 V
47NPS-2 Pickup
0.95
47NPS-2 Drop out Ratio
0.50 sec
47NPS-2 Time Delay
OFF
59N Definite Time delay
OFF
59N Inverse Time delay
Measured Vx
Disp. Voltage derived
from
5.0 V
59N DT-1 Pickup
0.95
59N DT-1 Dropout Ratio
0.01 sec
59N DT-1 Trip Time Delay
15.0 V
59N DT-2 Pickup
0.95
59N DT-2 Dropout Ratio
0.01 sec
59N DT-2 Trip Time Delay
5.0 V
59N IT Pickup
0.95
59N IT Dropout Ratio
1.0
59N IT Time Dial
5.00 sec
59N IT Reset time
0.00 sec
Constant time adder 67N-
TOC
OFF
50 1Ph
50 1Ph-2 Pickup
50 1Ph-2 Time Delay
50 1Ph-1 Pickup
50 1Ph-1 Time Delay
OFF
Recloser capacitor Test
5.0 sec
Capacitor voltage holdup
time
48 hour
Capacitor test time
interval
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading