Functions
2.3 Directional Overcurrent Protection 67, 67N
[7sc80-gerumz-igr-20120314, 2, en_US]
Figure 2-25
If parameter 1513 MANUAL CLOSE is set to 67-1 instant. and manual close detection applies, the trip is
initiated as soon as the pickup conditions arrive, even if the element is blocked via a binary input.
The same applies to 79 AR 67-1 instantaneous.
The dropout delay does only function if no inrush was detected. An approaching inrush resets an already
running dropout time delay.
114
Logic diagram of the directional overcurrent element 67-1 for phases
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017