Figure 4-16
Example: result of a MinVal comparison of two input values
Table 4-4
Name
Input
X0
...
X9
Output
Y
Table 4-5
Name
Input
X0
...
X9
Output
Y0
...
Y9
Table 4-6
Name
Input
SIM_ON
SIM52_a
a_52
b_52
Output
Own_a
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
With the CFC block Fault Recorder Trigger, you can form a group indication of the connected
inputs. This happens because only positive edges (from 0 to 1) are recognized by the circuit
and these are combined via an OR operation
Type
BOOL
...
BOOL
BOOL
The CFC block Connector loops the values of up to 10 inputs X0 to X9 directly through to the
outputs Y0 to Y9. From 4 connections on, this Connector is more effective than the CONNECT
block.
Type
BOOL
...
BOOL
BOOL
...
BOOL
The CFC block Status Feedback switches between the inputs a_52 and b_52 and the status
SIM_52_A at Own_a and Own_b. By allocating the input SIM_ON to 1, the status of the input
SIM_52_a is forwarded to the outputs Own_a and Own_b.
Type
BOOL
BOOL
BOOL
BOOL
BOOL
Description
Dynamic input
...
Dynamic input
Result from OR
Description
Input
...
Input
Output
...
Output
Description
Simulation ON
0 => Own_a = a_52
=> Own_b = b_52
1 => Own_a = SIM52_ a
=> Own_b = not SIM52_a
Simulated a_52 value
1 if breaker closed
0 if breaker open
1 if breaker open
0 if breaker closed
Result from OR
Technical Data
4.22 User-defined Functions (CFC)
Default function
0
...
0
0
Default function
0
...
0
0
...
0
Default function
0
0
0
0
0