Special Parameters in
Easy Setting GUI View
Delayed Curve x Gnd
Min Operating Time
Delayed Curve x Phase
Enable Directional
Delayed Curve x Gnd
Enable Direct.
Delayed Curve x Phase
Directional
Delayed Curve x
Ground Directional
High Current Trip
Phase (∞ = disabled)
High Current Trip
Ground (∞ = disabled)
Time Delay High
Current Trip Phase
Time Delay High
Current Trip Ground
High Current Trip Ph
Disable Direction.
High Current Trip Gnd
Disable Direction.
High Current Trip
Phase Directional
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
0.00 .. 30.00 sec
YES
NO
YES
NO
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
1 A
0.10 .. 30.00 A; ∞
5 A
0.50 .. 150.00 A; ∞
1 A
0.05 .. 30.00 A; ∞
5 A
0.25 .. 150.00 A; ∞
0.00 .. 7200.00 sec; ∞
0.00 .. 60.00 sec; ∞
YES
NO
YES
NO
Forward
Reverse
Non-Directional
2.29 Recloser Setting Summary
Default Setting Description
0.01 sec
Set the minimum oper-
ating time for the
Delayed curve x
ground.
YES
This setting will determine
if the Delayed Curve x
phase would enable
direction judgement.
YES
This setting will determine
if the Delayed Curve x
ground would enable
direction judgement.
Forward
This setting will determine
that the Delayed Curve
x phase would pickup in
forward, reverse direction
or no-direction required.
Forward
This setting will determine
that the Delayed Curve
x ground would pickup
in forward, reverse direc-
tion or no-direction
required.
1.00 A
Set the minimum trip
values for the High
5.00 A
current phase.
0.20 A
Set the minimum trip
values for the High
1.00 A
current ground.
0.50 sec
Set the time delay value
for the High current
phase.
0.50 sec
Set the time delay value
for the High current
ground.
YES
This setting will determine
if the High current
phase would disable
direction judgement.
YES
This setting will determine
if the High current
ground would disable
direction judgement.
Forward
This setting will determine
that the High current
phase would pickup in
forward, reverse direction
or no-direction required.
Functions
413