Addr.
Parameter
1326
Recloser Curves
1330
50N/51N
1331
MofPU Res T/TEp
1332A
51N-1 measure.
1333
51N-1 PICKUP
1334
51N-1 T DIAL
1335
51N-1 Drop-out
1336
51N-1 IEC Cur.
1337
51N-1 T adder
1338A
51N-2 measure.
1339
51N-2 PICKUP
1340
51N-2 T DIAL
1341
51N-2 Drop-out
1342
51N-2 IEC Cur.
1343
51N-2 T adder
1344A
51N-3 measure.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
Fundamental
True RMS
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
Fundamental
True RMS
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
Fundamental
True RMS
2.2 Overcurrent Protection 50, 51, 50N, 51N
Default Setting
Comments
Curve A (101)
Recloser Curves
50N/51N
Multiple of Pickup <->
T/TEp
Fundamental
51N-1 measurement of
0.20 A
51N-1 Pickup
1.00 A
0.20 sec
51N-1 Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
51N-1 IEC Curve
0.00 sec
Constant time adder 51N-1
Fundamental
51N-2 measurement of
0.20 A
51N-2 Pickup
1.00 A
0.20 sec
51N-2 Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
51N-2 IEC Curve
0.00 sec
Constant time adder 51N-2
Fundamental
51N-3 measurement of
Functions