Siemens 7SC80 Manual page 178

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.5 Single-Phase Overcurrent Protection
Addr.
Parameter
1562
67-TOC-4 PU
1563
67-TOC-4 T DIAL
1564A
67-TOC-4 MEAS.
1565
67-TOC-4 Drop.
1566
67-TOC-4 IEC
1567
67-TOC-4 T add.
1568
67-TOC-1 ANSI
1569
67-TOC-1 Rec.
1570
67-TOC-2 ANSI
178
C
Setting Options
1A
0.10 .. 4.00 A; ∞
5A
0.50 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Fundamental
True RMS
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
Comments
1.00 A
67-TOC-4 Pickup
5.00 A
0.50 sec
67-TOC-4 Time Dial
Fundamental
67-TOC-4 measurement of
Disk Emulation
Drop-Out Characteristic
Normal Inverse
67-TOC-4 IEC Curve
0.00 sec
Constant time adder 67-
TOC-4
NO
67-TOC-1 ANSI Curve
NO
67-TOC-1 Recloser Curve
NO
67-TOC-2 ANSI Curve
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents