Functions
2.17 Fault Locator
for a maximum of 3 line sections (see Section
"Reactance per Unit Length").
Initiation of Measurement
Normally the fault location calculation is started when a directional or non-directional time overcurrent protec-
tion initiates a trip signal (address 8001 START = TRIP). However, it may also be initiated when pickup drops
out (address 8001 START = Pickup), e.g. when another protection element clears the fault. Irrespective of
this fact, calculation of the fault location can be triggered externally via a binary input. (FNo. 1106
Flt. Loc ) provided the device has picked up.

Settings

2.17.3
Addr.
Parameter
8001
START

Information List

2.17.4
No.
Information
1106
>Start Flt. Loc
1114
Rpri =
1115
Xpri =
1117
Rsec =
1118
Xsec =
1119
dist =
1120
d[%] =
1122
dist =
1123
FL Loop AG
1124
FL Loop BG
1125
FL Loop CG
1126
FL Loop AB
1127
FL Loop BC
1128
FL Loop CA
1132
Flt.Loc.invalid
316
2.1.6.2 Setting Notes
Setting Options
Pickup
TRIP
Type of
Comments
Informa-
tion
SP
>Start Fault Locator
VI
Flt Locator: primary RESISTANCE
VI
Flt Locator: primary REACTANCE
VI
Flt Locator: secondary RESISTANCE
VI
Flt Locator: secondary REACTANCE
VI
Flt Locator: Distance to fault
VI
Flt Locator: Distance [%] to fault
VI
Flt Locator: Distance to fault
OUT
Fault Locator Loop AG
OUT
Fault Locator Loop BG
OUT
Fault Locator Loop CG
OUT
Fault Locator Loop AB
OUT
Fault Locator Loop BC
OUT
Fault Locator Loop CA
OUT
Fault location invalid
under "Ground Impedance Ratios" and
Default Setting
Comments
Pickup
Start fault locator with
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
>Start