Siemens 7SC80 Manual page 628

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
406
BinIn CAPT.TIME
610
FltDisp.LED/LCD
611
Spont. FltDisp.
613A
Gnd O/Cprot. w.
614A
OP. QUANTITY 59
615A
OP. QUANTITY 27
616A
OP. Quan.59 S2
617A
OP. Quan.27 S2
618
Direct Control
620
Remote FwUpdate Device, General
640
Start image DD
700
GOOSE-Stop
702A
Fast IO-Box
710
EvLog Fill Lev1
628
Function
C
Setting Options
Osc. Fault Rec.
0.10 .. 5.00 sec; ∞
Device, General
Target on PU
Target on TRIP
Device, General
YES
NO
P.System Data
Ignd (measured)
1
3I0 (calcul.)
P.System Data
Vphph
1
Vphph selective
Vph-n
Vph-n selective
V1
P.System Data
V1
1
Vphph
Vphph selective
Vph-n
Vph-n selective
P.System Data
Vphph
1
Vphph selective
Vph-n
Vph-n selective
V1
P.System Data
V1
1
Vphph
Vphph selective
Vph-n
Vph-n selective
Device, General
NO
YES
Disabled
Enabled
Device, General
image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 8
image 9
Device, General
YES
NO
Device, General
OFF
ON
Device, General
10 .. 100 %
Default Setting
Comments
0.50 sec
Capture Time via Binary
Input
Target on PU
Fault Display on LED / LCD
NO
Spontaneous display of
flt.annunciations
Ignd (measured)
Ground Overcurrent
protection with
Vphph
Opera. Quantity for 59
Overvolt. Prot.
V1
Opera. Quantity for 27
Undervolt. Prot.
Vphph
Opera.Quan.for 59 Over-
volt.Prot.Side2
V1
Opera.Quan.for 27
Undervolt.Prot.Side2
NO
Direct control of open/
close buttons
Disabled
Remote firmware update
image 1
Start image Default
Display
NO
GOOSE-Stop
OFF
Fast GOOSE transmission
70 %
Threshold Fill level 1
Event Log
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017