Technical Data
4.22 User-defined Functions (CFC)
Table 4-7
Name
Input
Start
Reset
Freeze
Hours
Min
hSec
Output
MAXVAL
Y1
Table 4-8
Name
Input
AutoONin
GOOSE01
...
GOOSE20
LCOUT_ON
Output
Auto_ON
ComFault
GenLCOUT
General Limits
Description
Maximum number of all CFC charts
considering all task levels
Maximum number of all CFC charts
considering one task level
Maximum number of all CFC inputs
considering all charts
Maximum number of reset-resistant
flipflops
D_FF_MEMO
568
The CFC block Inhibited Long Timer is a long-time timer whose value can be frozen by setting
an additional pin.
Type
BOOL
BOOL
BOOL
UINT
UINT
UINT
BOOL
BOOL
The CFC block COMMS_CHECK supplies the ComFault output via an OR operation with the
value status NotValid of the GOOSE input.
Type
BOOL
STRUCT
...
STRUCT
BOOL
BOOL
BOOL
BOOL
Limit
32
16
400
350
Description
Starts or retriggers the timer (upon 0-1
transition)
Resets the timer
Freezes the timer
Value for full hours
Value for full hours
Value for full seconds
Value for full seconds
Timer still running
Description
Starts or retriggers the timer (upon 0-1
transition)
Consists of binary indication informa-
tion and status NotValid
...
Consists of binary indication informa-
tion and status NotValid
Lockout sets GenLCOUT
Pass-through of AutoONin dependent
on the status information of GOOSE01
to GOOSE20
Set dependent on the status informa-
tion of GOOSE01 to GOOSE20
Set by at least one indication value or
LCOUT_ON
Comment
If the limit is exceeded, the device rejects the parameter
set with an error message, restores the last valid param-
eter set and restarts using that parameter set.
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring.
The red ERROR-LED lights up.
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring.
The red ERROR-LED lights up.
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring.
The red ERROR-LED lights up.
E50417-G1140-C486-A8, Edition 07.2017
Default function
0
0
0
0
0
0
0
0
Default function
0
0.0
...
0.0
0
0
0
0
SIPROTEC Compact, 7SC80, Manual

Hide quick links: