Addr.
Parameter
1613A
MANUAL CLOSE
1614A
67N-2 active
1617
67N POLARIZAT.
1618A
67N T DROP-OUT
1619A
ROTATION ANGLE
1620A
67N-2 MEASUREM.
1621A
67N-1 MEASUREM.
1622A
67N-TOC MEASUR.
1623
67N-2 Direction
1624
67N-1 Direction
1625
67N-TOC Direct.
1626
Recloser Curves
1630
M.of PU TD
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
67N-3 instant.
67N-2 instant.
67N-1 instant.
67N-TOC instant
67N-TOC-1 inst.
67N-TOC-2 inst.
67N-TOC-3 inst.
67N-TOC-4 inst.
Inactive
always
with 79 active
with VN and IN
with V2 and I2
0.00 .. 60.00 sec
-180 .. 180 °
Fundamental
True RMS
Fundamental
True RMS
Fundamental
True RMS
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
2.5 Single-Phase Overcurrent Protection
Default Setting
Comments
67N-3 instant.
Manual Close Mode
always
67N-2 active
with VN and IN
Ground Polarization
0.00 sec
67N Drop-Out Time Delay
-45 °
Rotation Angle of Refer-
ence Voltage
Fundamental
67N-2 measurement of
Fundamental
67N-1 measurement of
Fundamental
67N-TOC measurement of
Forward
67N-2 Direction
Forward
67N-1 Direction
Forward
67N-TOC Direction
Curve A (101)
Recloser Curves
Multiples of PU Time-Dial
Functions
181

Hide quick links:

Advertisement

Table of Contents
loading