Functions
2.5 Single-Phase Overcurrent Protection
Addr.
Parameter
1522A
67-TOC MEASUR.
1523
67-2 Direction
1524
67-1 Direction
1525
67-TOC Direct.
1526
Recloser Curves
1530
67
1531
MofPU Res T/Tp
1534
67-3 PICKUP
1535
67-3 DELAY
1536
67-3 Direction
1537A
67-3 MEASUREM.
1538
67-3 w. Inrush
1539A
67-3 active
1540
67-TOC-1 Dir.
1541
67-TOC-2 Dir.
176
C
Setting Options
Fundamental
True RMS
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
1A
1.00 .. 30.00 A; ∞
5A
5.00 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
Forward
Reverse
Non-Directional
Fundamental
True RMS
NO
YES
with 79 active
always
Forward
Reverse
Non-Directional
Forward
Reverse
Non-Directional
Default Setting
Comments
Fundamental
67-TOC measurement of
Forward
67-2 Direction
Forward
67-1 Direction
Forward
67-TOC Direction
Curve A (101)
Recloser Curves
67
Multiple of Pickup <-> T/Tp
∞ A
67-3 Pickup
∞ A
0.00 sec
67-3 Time Delay
Forward
67-3 Direction
Fundamental
67-3 measurement of
NO
67-3 with Inrush Restraint
always
67-3 active
Forward
67-TOC-1 Direction
Forward
67-TOC-2 Direction
SIPROTEC Compact, 7SC80, Manual