Siemens 7SC80 Manual page 424

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.29 Recloser Setting Summary
Special Parameters in
Easy Setting GUI View
PTx Secondary Voltage
PT A Phase Angle
Correction
PT B Phase Angle
Correction
PT C Phase Angle
Correction
PT A Phase Angle
Correction Side2
PT B Phase Angle
Correction Side2
PT C Phase Angle
Correction Side2
PTx Phase Angle
Correction
PT A Correction Factor
PT B Correction Factor
PT C Correction Factor
PT A Correction Factor
Side2
PT B Correction Factor
Side2
PT C Correction Factor
Side2
PT x Correction Factor
424
C
Setting Options
34 .. 230 V
-90.00 .. 90.00 °
-90.00 .. 90.00 °
-90.00 .. 90.00 °
-90.00 .. 90.00 °
-90.00 .. 90.00 °
-90.00 .. 90.00 °
-90.00 .. 90.00 °
0.5000 .. 2.0000
0.5000 .. 2.0000
0.5000 .. 2.0000
0.5000 .. 2.0000
0.5000 .. 2.0000
0.5000 .. 2.0000
0.5000 .. 2.0000
Default Setting Description
100 V
Set the PTx secondary
voltage value.
0.00 °
Set the PT phase A
angle correction.
0.00 °
Set the PT phase B
angle correction.
0.00 °
Set the PT phase C
angle correction.
0.00 °
Set the PT phase A
angle correction
side 2.
0.00 °
Set the PT phase B
angle correction
side 2.
0.00 °
Set the PT phase C
angle correction
side 2.
0.00 °
Set the PTx phase
angle correction.
1.0000
Set the PT phase A
correction factor.
1.0000
Set the PT phase B
correction factor.
1.0000
Set the PT phase C
correction factor.
1.0000
Set the PT phase A
correction factor
side 2.
1.0000
Set the PT phase B
correction factor
side 2.
1.0000
Set the PT phase C
correction factor
side 2.
1.0000
Set the PTx correction
factor.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017