Functions
2.5 Single-Phase Overcurrent Protection
Addr.
Parameter
1575
67-TOC-4 Rec.
1601
FCT 67N/67N-TOC
1602
67N-2 PICKUP
1603
67N-2 DELAY
1604
67N-1 PICKUP
1605
67N-1 DELAY
1607
67N-TOC PICKUP
1608
67N-TOC T-DIAL
1608
67N-TOC T-DIAL
1609
67N-TOC T-DIAL
1610
67N-TOC DropOut
1611
67N-TOC IEC
1612
67N-TOC ANSI
180
C
Setting Options
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
OFF
ON
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.01 .. 20.00 sec; ∞
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
Comments
NO
67-TOC-4 Recloser Curve
OFF
67N, 67N-TOC Ground
Time Overcurrent
0.50 A
67N-2 Pickup
2.50 A
0.10 sec
67N-2 Time Delay
0.20 A
67N-1 Pickup
1.00 A
0.50 sec
67N-1 Time Delay
0.20 A
67N-TOC Pickup
1.00 A
0.20 sec
67N-TOC Time Dial
0.20 sec
67N-TOC Time Dial
5.00
67N-TOC Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Very Inverse
ANSI Curve