Settings; Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

The TRIP command of a protection function that is not parameterized as AR initiation function leads to a 3-pole
final TRIP command. The 1-pole TRIP is only permitted if the affected phase can be identified. The time over-
current protection ground and sensitive ground fault protection functions cannot determine the faulty phase.
2-pole TRIP commands are allowed in 1PTrip-1PLO mode. Every fault that affects more than one phase
results in a TRIP of these phases. If a protection function on a second phase trips during a 1-pole AR dead time
which would also result in a 1-pole AR, the CLOSE commands for the two poles are combined. The longer dead
time of the two affected phases will be used.
If a 1-pole AR cycle was unsuccessful and the final TRIP is reached, this only affects the corresponding phase.
In this case, the 7SC80 does not force a 3-pole TRIP.
Table 2-21
1stcondition:
Pending TRIP from initiation func-
tion time overcurrent protection
ground or sensitive ground fault
protection
Pending TRIP from initiation func-
tion time overcurrent protection on
one phase X
Pending TRIP from initiation func-
tion time overcurrent protection on
two phases X, Y
Pending TRIP from initiation func-
tion time overcurrent protection on
one phase X
A non-initiation function such as
frequency protection or voltage
protection detected a fault
2.16.3

Settings

Addr.
Parameter
7400
Triple/Single

Information List

2.16.4
No.
Information
2584
>52a-Ph1
2585
>52a-Ph2
2586
>52a-Ph3
2587
>52b-Ph1
2588
>52b-Ph2
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Reaction of the 3-/1-pole operation function to different system faults
2ndcondition:
No other function picks up
Fault on one phase detected by
initiation function
Fault on two phases detected by
initiation function
Fault on three phases detected by
initiation function
No other function picked up or
initiation function sensitive ground
fault protection or time overcurrent
protection ground picked up
No other function picked up or
initiation function sensitive ground
fault protection or time overcurrent
protection ground picked up
2-pole fault detected by AR initia-
tion function
Setting Options
3PTrip-3PLO
1PTrip-3PLO
1PTrip-1PLO
Type of
Informa-
tion
SP
SP
SP
SP
SP
Reaction:
3-pole TRIP and 3-pole AR
1-pole TRIP and 1-pole AR
2-pole TRIP and 2-pole AR
3-pole TRIP and 3-pole AR
1-pole TRIP and 1-pole AR
2-pole TRIP and 2-pole AR
3-pole TRIP and 3-pole AR
3-pole TRIP and final TRIP
Default Setting
Comments
3PTrip-3PLO
Triple/Single Mode
Comments
>52a-Ph1 Contact (OPEN, if bkr is open)
>52a-Ph2 Contact (OPEN, if bkr is open)
>52a-Ph3 Contact (OPEN, if bkr is open)
>52b Ph1 Contact(CLOSED, if bkr is open)
>52b Ph2 Contact(CLOSED, if bkr is open)
Functions
2.16 Triple Single Mode
311