Siemens 7SC80 Manual page 101

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
1283
51-4 ANSI Curve
1284
51-4 Rec. Curve
1285
51-1 Min O. T
1286
51-2 Min O. T
1287
51-3 Min O. T
1288
51-4 Min O. T
1301
FCT 50N/51N
1302
50N-2 PICKUP
1303
50N-2 DELAY
1304
50N-1 PICKUP
1305
50N-1 DELAY
1307
51N PICKUP
1308
51N TIME DIAL
1308
51N TIME DIAL
1309
51N TIME DIAL
1310
51N Drop-out
1311
51N IEC CURVE
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
C
Setting Options
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
NO
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
0.00 .. 30.00 sec
0.00 .. 30.00 sec
0.00 .. 30.00 sec
0.00 .. 30.00 sec
ON
OFF
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 30.00 A; ∞
5A
0.25 .. 150.00 A; ∞
0.00 .. 60.00 sec; ∞
1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
0.05 .. 3.20 sec; ∞
0.01 .. 20.00 sec; ∞
0.50 .. 15.00 ; ∞
Instantaneous
Disk Emulation
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
2.2 Overcurrent Protection 50, 51, 50N, 51N
Default Setting
Comments
NO
51-4 ANSI Curve
NO
51-4 Recloser Curve
0.01 sec
Min Operating Time 51-1
0.01 sec
Min Operating Time 51-2
0.01 sec
Min Operating Time 51-3
0.01 sec
Min Operating Time 51-4
ON
50N, 51N Ground Time
Overcurrent
0.50 A
50N-2 Pickup
2.50 A
0.10 sec
50N-2 Time Delay
0.20 A
50N-1 Pickup
1.00 A
0.50 sec
50N-1 Time Delay
0.20 A
51N Pickup
1.00 A
0.20 sec
51N Time Dial
0.20 sec
51N Time Dial
5.00
51N Time Dial
Disk Emulation
Drop-Out Characteristic
Normal Inverse
IEC Curve
Functions
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents