Functions
2.14 Automatic Reclosing System 79
Addr.
Parameter
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
7138
Internal SYNC
7139
External SYNC
7140
ZONE SEQ.COORD.
7150
50-1
7151
50N-1
7152
50-2
7153
50N-2
7154
51
7155
51N
7156
67-1
7157
67N-1
7158
67-2
284
Setting Options
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0.01 .. 320.00 sec
0 .. 9
0 .. 9
(Setting options depend on
configuration)
(Setting options depend on
configuration)
YES
NO
OFF
ON
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
No influence
Starts 79
Stops 79
Default Setting
Comments
0.50 sec
Dead Time 1: Phase Fault
0.50 sec
Dead Time 1: Ground Fault
0.50 sec
Dead Time 2: Phase Fault
0.50 sec
Dead Time 2: Ground Fault
0.50 sec
Dead Time 3: Phase Fault
0.50 sec
Dead Time 3: Ground Fault
0.50 sec
Dead Time 4: Phase Fault
0.50 sec
Dead Time 4: Ground Fault
1
Number of Reclosing Cycles
Ground
1
Number of Reclosing Cycles Phase
none
Close command via control device
none
Internal 25 synchronisation
NO
External 25 synchronisation
OFF
ZSC - Zone sequence coordination
No influence
50-1
No influence
50N-1
No influence
50-2
No influence
50N-2
No influence
51
No influence
51N
No influence
67-1
No influence
67N-1
No influence
67-2
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017