2.26 Auxiliary Functions

Average Measurements

2.26.4
The long-term averages are calculated and output by the 7SC80.
2.26.4.1

Description

Long-Term Averages
The long-term averages of the three phase currents Ι
phase currents, and the real power P, reactive power Q, and apparent power S are calculated within a set
period of time and indicated in primary values.
For the long-term averages mentioned above, the length of the time window for averaging and the frequency
with which it is updated can be set.
2.26.4.2

Setting Notes

Average Calculation
The selection of the time period for measured value averaging is set with parameter 8301 DMD Interval in
the corresponding setting group A to P under MEASUREMENT. The first number specifies the averaging time
window in minutes while the second number gives the frequency of updates within the time window. 15
Min., 3 Subs, for example, means: time average is generated for all measured values within a window of
15 minutes. The output is updated every 15/3 = 5 minutes.
With address 8302 DMD Sync.Time, the starting time for the averaging window set under address 8301 is
determined. This setting specifies if the window should start on the hour (On The Hour) or 15 minutes later
(15 After Hour) or 30 minutes / 45 minutes after the hour (30 After Hour, 45 After Hour).
If the settings for averaging are changed, then the measured values stored in the buffer are deleted, and new
results for the average calculation are only available after the set time period has passed.
2.26.4.3

Settings

Addr.
Parameter
8301
DMD Interval
8302
DMD Sync.Time
2.26.4.4

Information List

No.
Information
833
I1 dmd=
834
P dmd =
835
Q dmd =
836
S dmd =
963
Ia dmd=
964
Ib dmd=
376
Setting Options
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
On The Hour
15 After Hour
30 After Hour
45 After Hour
Type of
Comments
Informa-
tion
MV
I1 (positive sequence) Demand
MV
Active Power Demand
MV
Reactive Power Demand
MV
Apparent Power Demand
MV
I A demand
MV
I B demand
, the positive sequence components Ι
x
Default Setting
Comments
60 Min., 1 Sub
Demand Calculation Intervals
On The Hour
Demand Synchronization Time
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
for the three
1