Settings; Information List; Settings Groups; Description - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

If the binary input time is set to ∞, the length of the record equals the time that the binary input is activated
(static), but not longer than the MAX. LENGTH (address 403).
2.1.4.3

Settings

Addr.
Parameter
401
WAVEFORMTRIGGER
402
WAVEFORM DATA
403
MAX. LENGTH
404
PRE. TRIG. TIME
405
POST REC. TIME
406
BinIn CAPT.TIME
2.1.4.4

Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
203
Wave. deleted
30053
Fault rec. run.

Settings Groups

2.1.5
Up to 16 different setting groups can be created for establishing the device's function settings.
2.1.5.1

Description

Changing Setting Groups
The setting groups can be changed during operation locally via the Web Monitor, via binary inputs (if config-
ured correspondingly), or via the interfaces. For safety reasons, it is not possible to change between setting
groups during a power system fault.
A setting group includes the parameter values for all functions that have been selected as Enabled during
configuration (see Section
are supported. Whereas the setting values may vary, the selected functions of each setting group remain the
same.
2.1.5.2

Setting Notes

General
If the setting group change option is not required, Group A is the default selection. Then, the rest of this
section is not applicable.
If the changeover option is desired, group changeover must be set to Grp Chge OPTION = Enabled
(address 103) when the function extent is configured. For the setting of the function parameters, each of the
required setting groups A to P (a maximum of 16) must be configured in sequence. The SIPROTEC 4 System
Description gives further information on how to copy setting groups or reset them to their status at delivery
and also how to change from one setting group to another.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Setting Options
Save w. Pickup
Save w. TRIP
Start w. TRIP
Fault event
Pow.Sys.Flt.
0.30 .. 6.00 sec
0.05 .. 0.50 sec
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Type of
Comments
Informa-
tion
IntSP
Fault Recording Start
SP
>Trigger Waveform Capture
OUT_Ev
Waveform data deleted
OUT
Fault recording is running
2.1.1.2 Setting
Notes). In 7SC80 devices, 16 independent setting groups (A to P)
Default Setting
Comments
Save w. Pickup
Waveform Capture
Fault event
Scope of Waveform Data
2.00 sec
Max. length of a Waveform
Capture Record
0.25 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Functions
2.1 General
63