Siemens 7SC80 Manual page 665

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr. Parameter
4005
46-2 DELAY
4006
46 IEC CURVE
4007
46 ANSI CURVE
4008
46-TOC PICKUP
4009
46-TOC TIMEDIAL
4010
46-TOC TIMEDIAL
4011
46-TOC RESET
4012A 46 T DROP-OUT
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
4204
49 Θ ALARM
4205
I ALARM
4207A Kτ-FACTOR
4208A T EMERGENCY
5001
FCT 59
5002
59-1 PICKUP
5003
59-1 PICKUP
5004
59-1 DELAY
5005
59-2 PICKUP
5006
59-2 PICKUP
5007
59-2 DELAY
5017A 59-1 DOUT RATIO
5018A 59-2 DOUT RATIO
5019
59-1 PICKUP V1
5020
59-2 PICKUP V1
5030
59-1 PhA Pickup
5031
59-1 PhA Pickup
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
46 Negative
0.00 .. 60.00 sec; ∞ 1.50 sec
Seq
46 Negative
Normal Inverse
Seq
Very Inverse
Extremely Inv.
Long Inverse
46 Negative
Extremely Inv.
Seq
Inverse
Moderately Inv.
Very Inverse
46 Negative
1A
0.10 .. 2.00 A
Seq
5A
0.50 .. 10.00 A
46 Negative
0.50 .. 15.00 ; ∞
Seq
46 Negative
0.05 .. 3.20 sec; ∞
Seq
46 Negative
Instantaneous
Seq
Disk Emulation
46 Negative
0.00 .. 60.00 sec
Seq
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
49 Th.Overload 1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
49 Th.Overload
1.0 .. 10.0
49 Th.Overload
10 .. 15000 sec
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
0.90 .. 0.99
27/59 O/U Volt.
20 .. 240 V
27/59 O/U Volt.
20 .. 240 V
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
Functions, Settings, Information
Default Setting
Comments
46-2 Time Delay
Extremely Inv.
IEC Curve
Extremely Inv.
ANSI Curve
0.90 A
46-TOC Pickup
4.50 A
5.00
46-TOC Time Dial
0.50 sec
46-TOC Time Dial
Instantaneous
46-TOC Drop Out
0.00 sec
46 Drop-Out Time Delay
OFF
49 Thermal overload
protection
1.10
49 K-Factor
100.0 min
Time Constant
90 %
49 Thermal Alarm Stage
1.00 A
Current Overload Alarm
Setpoint
5.00 A
1.0
Kt-FACTOR when motor
stops
100 sec
Emergency time
OFF
59 Overvoltage Protec-
tion
110 V
59-1 Pickup
110 V
59-1 Pickup
0.50 sec
59-1 Time Delay
120 V
59-2 Pickup
120 V
59-2 Pickup
0.50 sec
59-2 Time Delay
0.95
59-1 Dropout Ratio
0.95
59-2 Dropout Ratio
110 V
59-1 Pickup V1
120 V
59-2 Pickup V1
110 V
59-1 Phase A Pickup
110 V
59-1 Phase A Pickup
F.2 Settings
665