Technical Data
10.1
General Device Data
10.1.1 Analog Inputs
Current Inputs
Voltage Inputs
Analog Output
(for Measured
Values and
Fault Location)
10.1.2 Power Supply
Direct Voltage
10-2
Nominal frequency
Nominal current
I
N
Power consumption
per phase and earth path
– at I
= 1 A
N
– at I
= 5 A
N
– Sensitive earth fault detection at 1 A
Current overload capability per input
– thermal (rms)
– dynamic (pulse)
Current overload capability
for sensitive earth current input
– thermal (rms)
– dynamic (pulse)
Nominal voltage
U
N
Power consumption per phase at 100 V ≤0.1 VA
Overload capability per phase
– thermal (rms)
Range
– Connection for flush mounting
housing
for surface mounting housing
– max. load impedance
Voltage supply via integrated DC/DC converter:
Nominal power supply
direct voltage U
NDC
Permissible voltage ranges
f
50 Hz or 60 Hz(adjustable)
N
1 A or 5 A
approx. 0.05 VA
approx. 0.3 VA
approx. 0.05 VA
500 A for 1 s
150 A for 10 s
20 A continuous
1250 A (half cycle)
300 A for 1 s
100 A for 10 s
15 A continuous
750 A (half cycle)
80 V to 125 V (adjustable)
230 V continuous
0 to 24 mA–
rear panel, mounting location „B" or/and „D"
9-pin D-subminiture female connector
on case bottom or/and on case top
350 Ω
24/48 VDC
60/110/125 VDC
19 to 58 VDC
48 to 150 VDC
110/125/220/
250 VDC
88 to 300 VDC
7SA6 Manual
C53000-G1176-C133-1