Siemens 7SC80 Manual page 663

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr. Parameter
2803
Cap.recovery T
3101
Sens. Gnd Fault
3102
CT Err. I1
3102
CT Err. I1
3103
CT Err. F1
3104
CT Err. I2
3104
CT Err. I2
3105
CT Err. F2
3106
VPH MIN
3107
VPH MAX
3109
64-1 VGND
3110
64-1 VGND
3111
T-DELAY Pickup
3112
64-1 DELAY
3113
50Ns-2 PICKUP
3113
50Ns-2 PICKUP
3114
50Ns-2 DELAY
3115
67Ns-2 DIRECT
3117
50Ns-1 PICKUP
3117
50Ns-1 PICKUP
3118
50Ns-1 DELAY
3119
51Ns PICKUP
3119
51Ns PICKUP
3120
51NsTIME DIAL
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
Recl. Cap. Test
1.0 .. 60.0 sec
Sens. Gnd Fault
OFF
ON
ON with GF log
Alarm Only
Sens. Gnd Fault 1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
Sens. Gnd Fault 1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
Sens. Gnd Fault
0.0 .. 5.0 °
Sens. Gnd Fault 1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
Sens. Gnd Fault 1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
Sens. Gnd Fault
0.0 .. 5.0 °
Sens. Gnd Fault
10 .. 100 V
Sens. Gnd Fault
10 .. 100 V
Sens. Gnd Fault
1.8 .. 200.0 V; ∞
Sens. Gnd Fault
5.0 .. 225.0 V; ∞
Sens. Gnd Fault
0.04 .. 320.00 sec;
Sens. Gnd Fault
0.10 ..
40000.00 sec; ∞
Sens. Gnd Fault 1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
Sens. Gnd Fault 1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
Sens. Gnd Fault
0.00 .. 320.00 sec;
Sens. Gnd Fault
Forward
Reverse
Non-Directional
Sens. Gnd Fault 1A
0.001 .. 1.600 A
5A
0.005 .. 8.000 A
Sens. Gnd Fault 1A
0.05 .. 30.00 A
5A
0.25 .. 150.00 A
Sens. Gnd Fault
0.00 .. 320.00 sec;
Sens. Gnd Fault 1A
0.001 .. 1.400 A
5A
0.005 .. 7.000 A
Sens. Gnd Fault 1A
0.05 .. 4.00 A
5A
0.25 .. 20.00 A
Sens. Gnd Fault
0.10 .. 4.00 sec; ∞
Functions, Settings, Information
Default Setting
Comments
10.0 sec
Capacitor voltage
recovery time
OFF
(Sensitive) Ground Fault
0.050 A
Current I1 for CT Angle
Error
0.250 A
1.00 A
Current I1 for CT Angle
Error
5.00 A
0.0 °
CT Angle Error at I1
1.000 A
Current I2 for CT Angle
Error
5.000 A
10.00 A
Current I2 for CT Angle
Error
50.00 A
0.0 °
CT Angle Error at I2
40 V
L-Gnd Voltage of Faulted
Phase Vph Min
75 V
L-Gnd Voltage of
Unfaulted Phase Vph Max
40.0 V
64-1 Ground Displace-
ment Voltage
70.0 V
64-1 Ground Displace-
ment Voltage
1.00 sec
Time-DELAY Pickup
10.00 sec
64-1 Time Delay
0.300 A
50Ns-2 Pickup
1.500 A
10.00 A
50Ns-2 Pickup
50.00 A
1.00 sec
50Ns-2 Time Delay
Forward
67Ns-2 Direction
0.100 A
50Ns-1 Pickup
0.500 A
2.00 A
50Ns-1 Pickup
10.00 A
2.00 sec
50Ns-1 Time delay
0.100 A
51Ns Pickup
0.500 A
1.00 A
51Ns Pickup
5.00 A
1.00 sec
51Ns Time Dial
F.2 Settings
663