Addr. Parameter
1226
Recloser Curves
1230
51/51N
1231
MofPU Res T/Tp
1232A 51-1 measurem.
1233
51-1 PICKUP
1234
51-1 TIME DIAL
1235
51-1 Drop-out
1236
51-1 IEC Curve
1237A 51-1V Influence
1238A 51-1V V<
1239
51-1 Time adder
1240
Capacitor Ctrl.
1241
T Startup
1242
TD ON Command
1243
T ON/OFF CMD
1244A 51-2 measurem.
1245
51-2 PICKUP
1246
51-2 TIME DIAL
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
50/51 Overcur.
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
50/51 Overcur.
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
50/51 Overcur.
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur. 1A
0.02 .. 4.00 A; ∞
5A
0.10 .. 20.00 A; ∞
50/51 Overcur.
0.01 .. 20.00 sec; ∞ 0.50 sec
50/51 Overcur.
Instantaneous
Disk Emulation
50/51 Overcur.
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
50/51 Overcur.
NO
Volt. controll.
Volt. restraint
50/51 Overcur.
10.0 .. 125.0 V
50/51 Overcur.
0.00 .. 30.00 sec
Capacitor Ctrl.
OFF
ON
Capacitor Ctrl.
0.00 .. 3600.00 sec 5.00 sec
Capacitor Ctrl.
0.0 .. 60.0 min
Capacitor Ctrl.
0.00 .. 900.00 sec
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur. 1A
0.02 .. 4.00 A; ∞
5A
0.10 .. 20.00 A; ∞
50/51 Overcur.
0.01 .. 20.00 sec; ∞ 0.50 sec
Functions, Settings, Information
Default Setting
Comments
Curve A (101)
Recloser Curves
51/51N
Multiple of Pickup <->
T/Tp
Fundamental
51-1 measurement of
1.00 A
51-1 Pickup
5.00 A
51-1 Time Dial
Disk Emulation
Drop-out characteristic
Normal Inverse
51-1 IEC Curve
NO
51-1V Voltage Influence
50.0 V
51-1V V<Threshold for
Release Ip
0.00 sec
Constant time adder 51-1
OFF
Capacitor Control
Startup Time Device
1.0 min
ON command delay time
10.00 sec
ON/OFF command time
Fundamental
51-2 measurement of
1.00 A
51-2 Pickup
5.00 A
51-2 Time Dial
F.2 Settings