Siemens 7SC80 Manual page 414

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.29 Recloser Setting Summary
Special Parameters in
Easy Setting GUI View
High Current Trip
Ground Directional
High Current Lockout
Ph. (∞ = disabled)
High Current Lockout
Gnd (∞ = disabled)
Time Delay High
Current Lockout Phase
Time Delay High
Current Lockout
Ground
Minimum Trip Fast
Curve y Phase
Minimum Trip Fast
Curve y Ground
414
C
Setting Options
Forward
Reverse
Non-Directional
1 A
0.10 .. 30.00 A; ∞
5 A
0.50 .. 150.00 A; ∞
1 A
0.05 .. 30.00 A; ∞
5 A
0.25 .. 150.00 A; ∞
0.00 .. 7200.00 sec; ∞
0.00 .. 7200.00 sec; ∞
1 A
0.10 .. 4.00 A; ∞
5 A
0.50 .. 20.00 A; ∞
1 A
0.05 .. 4.00 A; ∞
5 A
0.25 .. 20.00 A; ∞
Default Setting Description
Forward
This setting will determine
that the High current
ground would pickup in
forward, reverse direction
or no-direction required.
4.00 A
Set the lockout values for
the High current
20.00 A
phase.
0.50 A
Set the lockout values for
the High current
2.50 A
ground.
0.00 sec
Set the lockout time delay
for the High current
phase.
0.10 sec
Set the lockout time delay
for the High current
ground.
1.00 A
Set the minimum trip
values for the Fast
5.00 A
curve y phase.
0.20 A
Set the minimum trip
values for the Fast
1.00 A
curve y ground.
SIPROTEC Compact, 7SC80, Manual