Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Addr.
Parameter
5714
27-1Ph2B Pickup
5715
27-1Ph2B Pickup
5716
27-1Ph2C Pickup
5717
27-1Ph2C Pickup
5718
27-2Ph2A Pickup
5719
27-2Ph2A Pickup
5720
27-2Ph2B Pickup
5721
27-2Ph2B Pickup
5722
27-2Ph2C Pickup
5723
27-2Ph2C Pickup
5724
27-1 Ph2A Delay
5725
27-1 Ph2B Delay
5726
27-1 Ph2C Delay
5727
27-2 Ph2A Delay
5728
27-2 Ph2B Delay
5729
27-2 Ph2C Delay
2.30.2.7

Information List

No.
Information
640.4101 27,59blkS2
31261
>BLOCK 27 S2
31262
>27 I SUP. S2
31263
>BLOCK 27-1 S2
31264
>BLOCK 27-2 S2
31265
27 OFF S2
31266
27 BLOCKED S2
31267
27 ACTIVE S2
31268
27-1 PU S2
31269
27-1 PU CS S2
31270
27-2 PU S2
31271
27-2 PU CS S2
31272
27-1 TRIP S2
31273
27-2 TRIP S2
31274
>BLOCK 59 S2
31275
59 OFF S2
31276
59 BLOCKED S2
31277
59 ACTIVE S2
31278
59-1 PU S2
31279
59-1 TRIP S2
31280
59-2 PU S2
31281
59-2 TRIP S2
31283
27-1 Ph2A PU
31284
27-1 Ph2B PU
31285
27-1 Ph2C PU
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Setting Options
10 .. 210 V
10 .. 120 V
10 .. 210 V
10 .. 120 V
10 .. 210 V
10 .. 120 V
10 .. 210 V
10 .. 120 V
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
Type of
Comments
Informa-
tion
IntSP
27, 59 blocked via operation Side2
SP
>BLOCK 27 undervolt. prot. Side2
SP
>27-Switch current superv. ON Side2
SP
>BLOCK 27-1 Undervolt. prot. Side2
SP
>BLOCK 27-2 Undervolt. prot. Side2
OUT
27 Undervolt.prot.switched OFF Side2
OUT
27 Undervolt. prot. is BLOCKED Side2
OUT
27 Undervolt. prot. is ACTIVE Side2
OUT
27-1 Undervolt. picked up Side2
OUT
27-1 PICKUP w/curr. superv Side2
OUT
27-2 Undervolt. picked up Side2
OUT
27-2 PICKUP w/curr. superv Side2
OUT
27-1 Undervoltage TRIP Side2
OUT
27-2 Undervoltage TRIP Side2
SP
>BLOCK 59 overvolt. prot. Side2
OUT
59 Overvolt.prot.switched OFF Side2
OUT
59 Overvolt.prot.is BLOCKED Side2
OUT
59 Overvolt.prot.is ACTIVE Side2
OUT
59-1 Overvolt. picked up Side2
OUT
59-1 Overvolt. TRIP Side2
OUT
59-2 Overvolt. picked up Side2
OUT
59-2 Overvolt. TRIP Side2
OUT
27-1 Phase 2A Undervoltage pickup
OUT
27-1 Phase 2B Undervoltage pickup
OUT
27-1 Phase 2C Undervoltage pickup
2.30 Additional Applications with 6 Voltage Inputs
Default Setting
Comments
75 V
27-1 Phase 2B Pickup
45 V
27-1 Phase 2B Pickup
75 V
27-1 Phase 2C Pickup
45 V
27-1 Phase 2C Pickup
70 V
27-2 Phase 2A Pickup
40 V
27-2 Phase 2A Pickup
70 V
27-2 Phase 2B Pickup
40 V
27-2 Phase 2B Pickup
70 V
27-2 Phase 2C Pickup
40 V
27-2 Phase 2C Pickup
1.50 sec
27-1 Phase 2A Time Delay
1.50 sec
27-1 Phase 2B Time Delay
1.50 sec
27-1 Phase 2C Time Delay
0.50 sec
27-2 Phase 2A Time Delay
0.50 sec
27-2 Phase 2B Time Delay
0.50 sec
27-2 Phase 2C Time Delay
Functions
437