Addr. Parameter
1913
51Nc Recloser
1914
51Nc-1 PICKUP
1915
51Nc-1 T-DIAL
1916
51Nc-1 Drop-out
1917
51Nc-1 IEC Cu.
1918
51Nc-1 T adder
1919
51Nc-1 ANSI Cu.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
ColdLoadPickup
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
ColdLoadPickup 1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
ColdLoadPickup
0.01 .. 20.00 sec; ∞ 0.20 sec
ColdLoadPickup
Instantaneous
Disk Emulation
ColdLoadPickup
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
ColdLoadPickup
0.00 .. 30.00 sec
ColdLoadPickup
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Functions, Settings, Information
Default Setting
Comments
Curve A (101)
Recloser Curve
0.20 A
51Nc-1 Pickup
1.00 A
51Nc-1 Time Dial
Disk Emulation
Drop-out Characteristic
Normal Inverse
51Nc-1 IEC Curve
0.00 sec
Constant time adder
51Nc-1
NO
51Nc-1 ANSI Curve
F.2 Settings