Functions
2.29 Recloser Setting Summary
Special Parameters in
Easy Setting GUI View
Fast Curve y Ground
Fast Curve y Phase
Time Dial
Fast Curve y Ground
Time Dial
Fast Curve y Phase
Reset
Fast Curve y Ground
Reset
Fast Curve y Phase
Time Adder
Fast Curve y Ground
Time Adder
Fast Curve y Ph
Minimum Operating
Time
Fast Curve y Gnd
Minimum Operating
Time
416
C
Setting Options
IEC Curve - Normal Inverse
IEC Curve - Very Inverse
IEC Curve - Extremely Inverse
IEC Curve - Long Inverse
ANSI Curve - Inverse
ANSI Curve - Short Inverse
ANSI Curve - Long Inverse
ANSI Curve - Moderately Inverse
ANSI Curve - Very Inverse
ANSI Curve - Extremely Inverse
ANSI Curve - Definite Inverse
Recloser Curve - Curve A (101)
Recloser Curve - Curve B (117)
Recloser Curve - Curve C (133)
Recloser Curve - Curve D (116)
Recloser Curve - Curve E (132)
Recloser Curve - Curve K (162)
Recloser Curve - Curve N (104)
Recloser Curve - Curve R (105)
Recloser Curve - Curve W (138)
Recloser Curve - Curve 2 (135)
Recloser Curve - Curve 3 (140)
Recloser Curve - Curve 8 (113)
Recloser Curve - Curve 8* (111)
Recloser Curve - Curve 9 (131)
Recloser Curve - Curve 11 (141)
0.01 .. 20.00 sec; ∞
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
Instantaneous
Disk Emulation
0.00 .. 30.00 sec
0.00 .. 30.00 sec
0.00 .. 30.00 sec
0.00 .. 30.00 sec
Default Setting Description
IEC Curve -
Set the trip curve type for
Normal Inverse
the Fast curve y
ground.
0.50 sec
Set the time dial for the
Fast curve y phase.
0.20 sec
Set the time dial for the
Fast curve y ground.
Disk Emulation
Set the reset characteristic
for the Fast curve y
phase.
Disk Emulation
Set the reset characteristic
for the Fast curve y
ground.
0.00 sec
Set the time adder for the
Fast curve y phase.
0.00 sec
Set the time adder for the
Fast curve y ground.
0.01 sec
Set the minimum oper-
ating time for the Fast
curve y phase.
0.01 sec
Set the minimum oper-
ating time for the Fast
curve y ground.