2.15 Sectionalizer Function
Addr.
Parameter
9524
Min. Iph CLP
9525
Min. Ignd CLP
9526
T. to con. Trip
9527
Time to open
9528
Time to reset
2.15.4

Information List

No.
Information
31175
>BLK. Sec. CLP
31176
Sec. CLP OFF
31177
Sec. CLP BLK.
31178
Sec. CLP run.
31179
Sec. Dyn set.
31180
>BLOCK Sec.
31181
Sec. OFF
31182
Sec. BLOCKED
31183
Sec. picked up
31184
Sec. counter
31185
Sec. open
31186
Sec. ACTIVE
31188
Sec. Ia =
31189
Sec. Ib =
31190
Sec. Ic =
31191
Sec. In =
308
C
Setting Options
1A
0.04 .. 30.00 A; ∞
5A
0.20 .. 150.00 A; ∞
1A
0.04 .. 30.00 A; ∞
5A
0.20 .. 150.00 A; ∞
0.01 .. 30.00 sec
0.00 .. 360.00 sec
0.00 .. 360.00 sec
Type of
Comments
Informa-
tion
SP
>BLOCK Sec. Cold Load Pickup
OUT
Sec. Cold-Load-Pickup switched OFF
OUT
Sec. Cold-Load-Pickup is BLOCKED
OUT
Sec. Cold-Load-Pickup is RUNNING
OUT
Sec. Dynamic Settings are ACTIVE
SP
>BLOCK Sectionalizer
OUT
Sectionalizer switched OFF
OUT
Sectionalizer is BLOCKED
OUT
Sectionalizer picked up
VI
Sectionalizer counter
OUT
Sectionalizer open command
OUT
Sectionalizer is ACTIVE
VI
Primary Sectionalizer fault current Ia
VI
Primary Sectionalizer fault current Ib
VI
Primary Sectionalizer fault current Ic
VI
Primary Sectionalizer fault current In
Default Setting
Comments
4.00 A
Minimum Phase During
Cold Load
20.00 A
1.00 A
Minimum Neutral During
Cold Load
5.00 A
0.15 sec
Time to confirm trip
5.00 sec
Time to open command
10.00 sec
Time to reset after last
increase
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017