Siemens 7SC80 Manual page 636

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
1312
51N ANSI CURVE
1313A MANUAL CLOSE
1314A 50N-2 active
1315A 50N T DROP-OUT
1316A 50N-3 active
1317
50N-3 PICKUP
1318
50N-3 DELAY
1319A 50N-3 measurem.
1320A 50N-2 measurem.
1321A 50N-1 measurem.
1322A 51N measurem.
1325A 51N Time adder
636
Function
C
Setting Options
50/51 Overcur.
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
50/51 Overcur.
50N-3 instant.
50N-2 instant.
50N-1 instant.
51N instant.
51N-1 instant.
51N-2 instant.
51N-3 instant.
51N-4 instant.
Inactive
50/51 Overcur.
Always
With 79 Active
50/51 Overcur.
0.00 .. 60.00 sec
50/51 Overcur.
Always
with 79 active
50/51 Overcur. 1A
0.25 .. 30.00 A; ∞
5A
1.25 .. 150.00 A; ∞ ∞ A
50/51 Overcur.
0.00 .. 60.00 sec; ∞ 0.05 sec
50/51 Overcur.
Fundamental
True RMS
Instantaneous
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
Fundamental
True RMS
50/51 Overcur.
0.00 .. 30.00 sec
Default Setting
Comments
Very Inverse
ANSI Curve
50N-2 instant.
Manual Close Mode
Always
50N-2 active
0.00 sec
50N Drop-Out Time Delay
Always
50N-3 active
∞ A
50N-3 Pickup
50N-3 Time Delay
Fundamental
50N-3 measurement of
Fundamental
50N-2 measurement of
Fundamental
50N-1 measurement of
Fundamental
51N measurement of
0.00 sec
Constant time adder 51N
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents