Mounting and Commissioning

3.1 Mounting and Connections

3.1
Mounting and Connections
General
!
WARNING
Warning of improper transport, storage, installation or assembly of the device.
Failure to observe these precautions can result in death, personal injury, or serious material damage.
Trouble-free and safe use of this device depends on proper transport, storage, installation, and
²
assembly of the device according to the warnings in this device manual.
Of particular importance are the general installation and safety regulations for work in a high-voltage
²
environment (for example, ANSI, IEC, EN, DIN, or other national and international regulations). These
regulations must be observed.
3.1.1

Configuration Information

Prerequisites
For installation and connections the following conditions must be met:
The rated device data have been checked as recommended in the SIPROTEC 4 System Description. It has been
verified that these data comply with the power system data.
General Diagrams
Block diagrams for the terminal assignment of the 7SC80 are shown in Appendix
Connection examples for the current and voltage transformer circuits are provided in Appendix
Examples.
Voltage Connection Examples
Connection examples for voltage transformers are provided in Appendix A.3. It must be checked that the
configuration of the Power System Data 1 (Section
The normal connection is set at address 213 VT Connect. 3ph = Van, Vbn, Vcn.
When connecting an open delta winding of the voltage transformer set, address 213 VT Connect. 3ph =
Vab, Vbc, VGnd.
Binary Inputs and Outputs
The configuration options of the binary in- and outputs, i.e. the procedure for the individual adaptation to the
plant conditions, are described in the SIPROTEC 4 System Description. The connections to the plant are
dependent on this configuration. The presettings of the device are listed in Appendix
Protocol-dependent
configured message functions.
Setting Group Change
If binary inputs are used to change setting groups, please observe the following:
450
Functions. Please also check that the labeling strips on the front panel correspond to the
2.1.3.2 Setting
Notes) corresponds with the connections.
E50417-G1140-C486-A8, Edition 07.2017
B Terminal
Assignments.
C Connection
E Default Settings and
SIPROTEC Compact, 7SC80, Manual