Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.22 Tap Changer
Addr.
Parameter
1254
MaxNo TChg DOWN
1255
Tcrit. VoltLvl.

Information List

2.22.4
No.
Information
2546
Tap Up
2547
Tap Down
2548
MaxNUpStepsRea
2549
MaxNDownStepsRe
2550
VoltRes Mode ON
2551
VoltRed Mode ON
2552
TapUpStepCnt
2553
TapDownStepCnt
2566
TapChg UpEnable
2567
TapChg Up
2568
TapChg Down En.
2569
TapChg Down
2570
AUTO Mode ON
2571
SetVoltRestMode
2572
ResVoltRestMode
2573
SetVoltRedMode
2574
ResVoltRedMode
2575
Ext 27 UV PU
2576
Ext 59 OV PU
2577
IntVoltMeas
2578
Vol Level Crit.
2579
VoltRedTapUpEn
2580
Vmeas = Vthr
2581
Vmeas > Vthr
2582
Vmeas < Vthr
2583
Vmeas > Vmin
354
Setting Options
0 .. 100
0.00 .. 120.00 sec
Type of
Comments
Informa-
tion
OUT
Tap Up
OUT
Tap Down
OUT
Maximum number Up Step reached
OUT
Maximum number Down Step reached
OUT
Voltage restoration mode is ON
OUT
Voltage reduction mode is ON
VI
Tap up step counter
VI
Tap Down step counter
SP
Tap Changer up enable
SP
Tap Changer UP
SP
Tap Changer down enable
SP
Tap Changer Down
SP
Automatic Mode On
SP
Set voltage restoration mode
SP
Reset voltage restoration mode
SP
Set voltage reduction mode
SP
Reset voltage reduction mode
SP
External 27 Undervoltage pickup
SP
External 59 Overvoltage pickup
SP
Internal voltage measurement value
SP
Critical voltage level
SP
Voltage reduction Tap up enable
SP
Measured Voltage is equal to threshold
SP
Measured Volt. is greater than threshold
SP
Measured Voltage is less than threshold
SP
Measured Voltage is greater than minimum
Default Setting
Comments
10
Maximum number of Tap Changer
Down-Steps
20.00 sec
Time critical Voltage level
SIPROTEC Compact, 7SC80, Manual