Negative Sequence Protection 46; Definite Time Characteristic; Inverse Time Characteristic 46-Toc - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions

2.9 Negative Sequence Protection 46

2.9
Negative Sequence Protection 46
Negative sequence protection detects unbalanced loads on the system.
Applications
This protection function can be used to detect interruptions, short-circuits and polarity problems in the
connections to the current transformers.
It also allows to detect 1-phase and 2-phase faults with fault currents smaller than the maximum load
current.
Prerequisites
The unbalanced load protection takes effect when:
at least one phase current is greater than 0.1 x Ι
all phase currents are smaller than 10 x Ι
2.9.1

Definite Time characteristic

The definite time characteristic consists of two elements. As soon as the first settable threshold 46-1 PICKUP
is reached, a pickup message is output and time element 46-1 DELAY is started. When the second element
46-2 PICKUP is started, another message is output and time element 46-2 DELAY is initiated. Once either
time delay elapses, a trip signal is initiated.
[unabhaeng-ausl_charakt-des-schieflastschutzes-260602-kn, 1, en_US]
Figure 2-57
Settable Dropout Times
Pickup stabilization for the definite-time tripping characteristic 46-1, 46-2 can be accomplished by means of
settable dropout times. This facility is used in power systems with possible intermittent faults. Used together
with electromechanical relays, it allows different dropout responses to be adjusted and a time grading of
numerical and electromechanical relays to be implemented.

Inverse Time characteristic 46-TOC

2.9.2
The inverse time element is dependent on the ordered device version. It operates with IEC or ANSI character-
istic tripping curves. The curves and associated formulas are given in the Technical Data. When programming
208
Nom
Definite time characteristic for negative sequence protection
and
Nom
.
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents