Settings; Information List - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.30 Additional Applications with 6 Voltage Inputs
[Lo_60VTS_S2_New, 1, en_US]
Figure 2-149
2.30.4.3

Settings

Addr.
Parameter
5530
60VTS S2
5531
60VTS V2 S2
5532
60VTS I2 S2
5533
60VTS I1 loadS2
5534
60VTS I1 flt S2
5535
60VTS V1 S2
5536
60VTS Delay S2
5537
BLOCK PROT. S2
2.30.4.4

Information List

No.
Information
31341
>FAIL:Fdr VT S2
31342
>FAIL:BUS VTS2
446
Voltage-transformer monitoring of side 2
C
Setting Options
OFF
ON with NPS
7 .. 110 V
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
1A
0.10 .. 10.00 A
5A
0.50 .. 50.00 A
1 .. 110 V
0.03 .. 320.00 sec
NO
YES
Type of
Informa-
tion
SP
SP
Default Setting
OFF
7 V
0.10 A
0.50 A
0.10 A
0.50 A
10.00 A
50.00 A
15 V
10.00 sec
YES
Comments
>Failure: Feeder VT Side2
>Failure: Busbar VT Side2
E50417-G1140-C486-A8, Edition 07.2017
Comments
60VTS Voltage
Transf.Superv.Side2
60VTS Threshold V2 Side2
60VTS Threshold I2 Side2
60VTS Threshold I1 load
Side2
60VTS Threshold I1 fault
Side2
60VTS Threshold V1 Side2
60VTS Time Delay Side2
Block protection by 60VTS
Side2
SIPROTEC Compact, 7SC80, Manual