Functions
2.4 Dynamic Cold Load Pickup
Addr.
Parameter
2113
67Nc-TOC Recl.
2114
67Nc-TOC-1 PU
2115
67Nc-TOC-1 TD
2116
67Nc-TOC-1D.out
2117
67Nc-TOC-1 IEC
2118
67Nc-TOC-1 T a.
2119
67Nc-TOC-1 ANSI
164
C
Setting Options
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
Comments
Curve A (101)
Recloser Curve
1.00 A
67Nc-TOC-1 Pickup
5.00 A
0.50 sec
67Nc-TOC-1 Time Dial
Disk Emulation
Drop-out Characteristic
Normal Inverse
67Nc-TOC-1 IEC Curve
0.00 sec
Constant time adder 67Nc-
TOC-1
NO
67Nc-TOC-1 ANSI Curve
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017