Functions, Settings, Information
F.2 Settings
Addr. Parameter
5032
59-1 PhB Pickup
5033
59-1 PhB Pickup
5034
59-1 PhC Pickup
5035
59-1 PhC Pickup
5036
59-2 PhA Pickup
5037
59-2 PhA Pickup
5038
59-2 PhB Pickup
5039
59-2 PhB Pickup
5040
59-2 PhC Pickup
5041
59-2 PhC Pickup
5042
59-1 PhA Delay
5043
59-1 PhB Delay
5044
59-1 PhC Delay
5045
59-2 PhA Delay
5046
59-2 PhB Delay
5047
59-2 PhC Delay
5101
FCT 27
5102
27-1 PICKUP
5103
27-1 PICKUP
5106
27-1 DELAY
5110
27-2 PICKUP
5111
27-2 PICKUP
5112
27-2 DELAY
5113A 27-1 DOUT RATIO
5114A 27-2 DOUT RATIO
5120A CURRENT SUPERV.
5130
27-1 PhA Pickup
5131
27-1 PhA Pickup
5132
27-1 PhB Pickup
5133
27-1 PhB Pickup
5134
27-1 PhC Pickup
5135
27-1 PhC Pickup
5136
27-2 PhA Pickup
5137
27-2 PhA Pickup
5138
27-2 PhB Pickup
5139
27-2 PhB Pickup
5140
27-2 PhC Pickup
666
Function
C
Setting Options
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
20 .. 260 V
27/59 O/U Volt.
20 .. 150 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
OFF
ON
Alarm Only
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
0.00 .. 100.00 sec;
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
1.01 .. 3.00
27/59 O/U Volt.
OFF
ON
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
10 .. 210 V
27/59 O/U Volt.
10 .. 120 V
27/59 O/U Volt.
10 .. 210 V
Default Setting
Comments
110 V
59-1 Phase B Pickup
110 V
59-1 Phase B Pickup
110 V
59-1 Phase C Pickup
110 V
59-1 Phase C Pickup
120 V
59-2 Phase A Pickup
120 V
59-2 Phase A Pickup
120 V
59-2 Phase B Pickup
120 V
59-2 Phase B Pickup
120 V
59-2 Phase C Pickup
120 V
59-2 Phase C Pickup
0.50 sec
59-1 Phase A Time Delay
0.50 sec
59-1 Phase B Time Delay
0.50 sec
59-1 Phase C Time Delay
0.50 sec
59-2 Phase A Time Delay
0.50 sec
59-2 Phase B Time Delay
0.50 sec
59-2 Phase C Time Delay
OFF
27 Undervoltage Protec-
tion
75 V
27-1 Pickup
45 V
27-1 Pickup
1.50 sec
27-1 Time Delay
70 V
27-2 Pickup
40 V
27-2 Pickup
0.50 sec
27-2 Time Delay
1.20
27-1 Dropout Ratio
1.20
27-2 Dropout Ratio
ON
Current Supervision
75 V
27-1 Phase A Pickup
45 V
27-1 Phase A Pickup
75 V
27-1 Phase B Pickup
45 V
27-1 Phase B Pickup
75 V
27-1 Phase C Pickup
45 V
27-1 Phase C Pickup
70 V
27-2 Phase A Pickup
40 V
27-2 Phase A Pickup
70 V
27-2 Phase B Pickup
40 V
27-2 Phase B Pickup
70 V
27-2 Phase C Pickup
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017