Settings - Siemens 7SC80 Manual

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions
2.30 Additional Applications with 6 Voltage Inputs
2.30.2.6

Settings

Addr.
Parameter
5601
FCT 59 S2
5602
59-1 PICKUP S2
5603
59-1 PICKUP S2
5604
59-1 PU V1 S2
5605
59-1 DELAY S2
5606
59-2 PICKUP S2
5607
59-2 PICKUP S2
5608
59-2 PU V1 S2
5609
59-2 DELAY S2
5610A
59-1 DOUT S2
5611A
59-2 DOUT S2
5612
59-1Ph2A Pickup
5613
59-1Ph2A Pickup
5614
59-1Ph2B Pickup
5615
59-1Ph2B Pickup
5616
59-1Ph2C Pickup
5617
59-1Ph2C Pickup
5618
59-2Ph2A Pickup
5619
59-2Ph2A Pickup
5620
59-2Ph2B Pickup
5621
59-2Ph2B Pickup
5622
59-2Ph2C Pickup
5623
59-2Ph2C Pickup
5624
59-1 Ph2A Delay
5625
59-1 Ph2B Delay
5626
59-1 Ph2C Delay
5627
59-2 Ph2A Delay
5628
59-2 Ph2B Delay
5629
59-2 Ph2C Delay
5701
FCT 27 S2
5702
27-1 PICKUP S2
5703
27-1 PICKUP S2
5704
27-1 DELAY S2
5705
27-2 PICKUP S2
5706
27-2 PICKUP S2
5707
27-2 DELAY S2
5708A
27-1 DOUT S2
5709A
27-2 DOUT S2
5710A
CURRENT SUPERV.
5712
27-1Ph2A Pickup
5713
27-1Ph2A Pickup
436
Setting Options
OFF
ON
Alarm Only
20 .. 260 V
20 .. 150 V
20 .. 240 V
0.00 .. 100.00 sec; ∞
20 .. 260 V
20 .. 150 V
20 .. 240 V
0.00 .. 100.00 sec; ∞
0.90 .. 0.99
0.90 .. 0.99
20 .. 260 V
20 .. 150 V
20 .. 260 V
20 .. 150 V
20 .. 260 V
20 .. 150 V
20 .. 260 V
20 .. 150 V
20 .. 260 V
20 .. 150 V
20 .. 260 V
20 .. 150 V
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
0.00 .. 100.00 sec; ∞
OFF
ON
Alarm Only
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
10 .. 210 V
10 .. 120 V
0.00 .. 100.00 sec; ∞
1.01 .. 3.00
1.01 .. 3.00
OFF
ON
10 .. 210 V
10 .. 120 V
Default Setting
Comments
OFF
59 Overvoltage Protection Side2
110 V
59-1 Pickup Side2
110 V
59-1 Pickup Side2
110 V
59-1 Pickup V1 Side2
0.50 sec
59-1 Time Delay Side2
120 V
59-2 Pickup Side2
120 V
59-2 Pickup Side2
120 V
59-2 Pickup V1 Side2
0.50 sec
59-2 Time Delay Side2
0.95
59-1 Dropout Ratio Side2
0.95
59-2 Dropout Ratio Side2
110 V
59-1 Phase 2A Pickup
110 V
59-1 Phase 2A Pickup
110 V
59-1 Phase 2B Pickup
110 V
59-1 Phase 2B Pickup
110 V
59-1 Phase 2C Pickup
110 V
59-1 Phase 2C Pickup
120 V
59-2 Phase 2A Pickup
120 V
59-2 Phase 2A Pickup
120 V
59-2 Phase 2B Pickup
120 V
59-2 Phase 2B Pickup
120 V
59-2 Phase 2C Pickup
120 V
59-2 Phase 2C Pickup
0.50 sec
59-1 Phase 2A Time Delay
0.50 sec
59-1 Phase 2B Time Delay
0.50 sec
59-1 Phase 2C Time Delay
0.50 sec
59-2 Phase 2A Time Delay
0.50 sec
59-2 Phase 2B Time Delay
0.50 sec
59-2 Phase 2C Time Delay
OFF
27 Undervoltage Protection Side2
75 V
27-1 Pickup Side2
45 V
27-1 Pickup Side2
1.50 sec
27-1 Time Delay Side2
70 V
27-2 Pickup Side2
40 V
27-2 Pickup Side2
0.50 sec
27-2 Time Delay Side2
1.20
27-1 Dropout Ratio Side2
1.20
27-2 Dropout Ratio Side2
OFF
Current Supervision
75 V
27-1 Phase 2A Pickup
45 V
27-1 Phase 2A Pickup
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents