Addr. Parameter
5535
60VTS V1 S2
5536
60VTS Delay S2
5537
BLOCK PROT. S2
5601
FCT 59 S2
5602
59-1 PICKUP S2
5603
59-1 PICKUP S2
5604
59-1 PU V1 S2
5605
59-1 DELAY S2
5606
59-2 PICKUP S2
5607
59-2 PICKUP S2
5608
59-2 PU V1 S2
5609
59-2 DELAY S2
5610A 59-1 DOUT S2
5611A 59-2 DOUT S2
5612
59-1Ph2A Pickup
5613
59-1Ph2A Pickup
5614
59-1Ph2B Pickup
5615
59-1Ph2B Pickup
5616
59-1Ph2C Pickup
5617
59-1Ph2C Pickup
5618
59-2Ph2A Pickup
5619
59-2Ph2A Pickup
5620
59-2Ph2B Pickup
5621
59-2Ph2B Pickup
5622
59-2Ph2C Pickup
5623
59-2Ph2C Pickup
5624
59-1 Ph2A Delay
5625
59-1 Ph2B Delay
5626
59-1 Ph2C Delay
5627
59-2 Ph2A Delay
5628
59-2 Ph2B Delay
5629
59-2 Ph2C Delay
5701
FCT 27 S2
5702
27-1 PICKUP S2
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Function
C
Setting Options
Meas-
1 .. 110 V
urem.Superv
Meas-
0.03 .. 320.00 sec
urem.Superv
Meas-
NO
urem.Superv
YES
27/59 S2
OFF
ON
Alarm Only
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 240 V
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 240 V
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.90 .. 0.99
27/59 S2
0.90 .. 0.99
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
20 .. 260 V
27/59 S2
20 .. 150 V
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
0.00 .. 100.00 sec;
27/59 S2
OFF
ON
Alarm Only
27/59 S2
10 .. 210 V
Functions, Settings, Information
Default Setting
Comments
15 V
60VTS Threshold V1
Side2
10.00 sec
60VTS Time Delay Side2
YES
Block protection by 60VTS
Side2
OFF
59 Overvoltage Protec-
tion Side2
110 V
59-1 Pickup Side2
110 V
59-1 Pickup Side2
110 V
59-1 Pickup V1 Side2
0.50 sec
59-1 Time Delay Side2
120 V
59-2 Pickup Side2
120 V
59-2 Pickup Side2
120 V
59-2 Pickup V1 Side2
0.50 sec
59-2 Time Delay Side2
0.95
59-1 Dropout Ratio Side2
0.95
59-2 Dropout Ratio Side2
110 V
59-1 Phase 2A Pickup
110 V
59-1 Phase 2A Pickup
110 V
59-1 Phase 2B Pickup
110 V
59-1 Phase 2B Pickup
110 V
59-1 Phase 2C Pickup
110 V
59-1 Phase 2C Pickup
120 V
59-2 Phase 2A Pickup
120 V
59-2 Phase 2A Pickup
120 V
59-2 Phase 2B Pickup
120 V
59-2 Phase 2B Pickup
120 V
59-2 Phase 2C Pickup
120 V
59-2 Phase 2C Pickup
0.50 sec
59-1 Phase 2A Time Delay
0.50 sec
59-1 Phase 2B Time Delay
0.50 sec
59-1 Phase 2C Time Delay
0.50 sec
59-2 Phase 2A Time Delay
0.50 sec
59-2 Phase 2B Time Delay
0.50 sec
59-2 Phase 2C Time Delay
OFF
27 Undervoltage Protec-
tion Side2
75 V
27-1 Pickup Side2
F.2 Settings