Functions, Settings, Information
F.2 Settings
Addr. Parameter
7117
T-ACTION
7118
T DEAD DELAY
7127
DEADTIME 1: PH
7128
DEADTIME 1: G
7129
DEADTIME 2: PH
7130
DEADTIME 2: G
7131
DEADTIME 3: PH
7132
DEADTIME 3: G
7133
DEADTIME 4: PH
7134
DEADTIME 4: G
7135
# OF RECL. GND
7136
# OF RECL. PH
7137
Cmd.via control
7138
Internal SYNC
7139
External SYNC
7140
ZONE SEQ.COORD. 79M Auto Recl.
7150
50-1
7151
50N-1
7152
50-2
7153
50N-2
7154
51
7155
51N
674
Function
C
Setting Options
79M Auto Recl.
0.01 .. 320.00 sec;
79M Auto Recl.
0.0 .. 1800.0 sec; ∞ 1.0 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0.01 .. 320.00 sec
79M Auto Recl.
0 .. 9
79M Auto Recl.
0 .. 9
79M Auto Recl.
(Setting options
depend on configu-
ration)
79M Auto Recl.
(Setting options
depend on configu-
ration)
79M Auto Recl.
YES
NO
OFF
ON
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
79M Auto Recl.
No influence
Starts 79
Stops 79
Default Setting
Comments
∞ sec
Action time
Maximum Time Delay of
Dead-Time Start
0.50 sec
Dead Time 1: Phase Fault
0.50 sec
Dead Time 1: Ground
Fault
0.50 sec
Dead Time 2: Phase Fault
0.50 sec
Dead Time 2: Ground
Fault
0.50 sec
Dead Time 3: Phase Fault
0.50 sec
Dead Time 3: Ground
Fault
0.50 sec
Dead Time 4: Phase Fault
0.50 sec
Dead Time 4: Ground
Fault
1
Number of Reclosing
Cycles Ground
1
Number of Reclosing
Cycles Phase
none
Close command via
control device
none
Internal 25 synchronisa-
tion
NO
External 25 synchronisa-
tion
OFF
ZSC - Zone sequence
coordination
No influence
50-1
No influence
50N-1
No influence
50-2
No influence
50N-2
No influence
51
No influence
51N
SIPROTEC Compact, 7SC80, Manual