Siemens 7SC80 Manual page 648

Siprotec compact feeder protection and recloser controller
Hide thumbs Also See for 7SC80:
Table of Contents

Advertisement

Functions, Settings, Information
F.2 Settings
Addr. Parameter
1626
Recloser Curves
1630
M.of PU TD
1631
I/IEp Rf T/TEp
1634
67N-3 PICKUP
1635
67N-3 DELAY
1636
67N-3 Direction
1637A 67N-3 MEASUREM. 67 Direct. O/C
1638
67N-3 w. Inrush
1639A 67N-3 active
1640
67N-TOC-1 Dir.
1641
67N-TOC-2 Dir.
1642
67N-TOC-3 Dir.
1643
67N-TOC-4 Dir.
1644
67N-TOC-1 PU
1645
67N-TOC-1 TD
1646A 67N-TOC-1 MEAS.
648
Function
C
Setting Options
67 Direct. O/C
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
67 Direct. O/C
1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
67 Direct. O/C
0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
67 Direct. O/C
0.50 .. 30.00 A; ∞
67 Direct. O/C
0.00 .. 60.00 sec; ∞ 0.00 sec
67 Direct. O/C
Forward
Reverse
Non-Directional
Fundamental
True RMS
67 Direct. O/C
NO
YES
67 Direct. O/C
always
with 79 active
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
Forward
Reverse
Non-Directional
67 Direct. O/C
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
67 Direct. O/C
0.01 .. 20.00 sec; ∞ 0.50 sec
67 Direct. O/C
Fundamental
True RMS
Default Setting
Comments
Curve A (101)
Recloser Curves
Multiples of PU Time-Dial
67N TOC
∞ A
67N-3 Pickup
67N-3 Time Delay
Forward
67N-3 Direction
Fundamental
67N-3 measurement of
NO
67N-3 with Inrush
Restraint
always
67N-3 active
Forward
67N-TOC-1 Direction
Forward
67N-TOC-2 Direction
Forward
67N-TOC-3 Direction
Forward
67N-TOC-4 Direction
1.00 A
67N-TOC-1 Pickup
5.00 A
67N-TOC-1 Time Dial
Fundamental
67N-TOC-1 measurement
of
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017

Hide quick links: