Functions
2.4 Dynamic Cold Load Pickup
Addr.
Parameter
1912
51Nc ANSI
1913
51Nc Recloser
1914
51Nc-1 PICKUP
1915
51Nc-1 T-DIAL
1916
51Nc-1 Drop-out
1917
51Nc-1 IEC Cu.
1918
51Nc-1 T adder
1919
51Nc-1 ANSI Cu.
160
C
Setting Options
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
1A
0.05 .. 4.00 A; ∞
5A
0.25 .. 20.00 A; ∞
0.01 .. 20.00 sec; ∞
Instantaneous
Disk Emulation
NO
Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
0.00 .. 30.00 sec
NO
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Default Setting
Comments
Very Inverse
ANSI Curve
Curve A (101)
Recloser Curve
0.20 A
51Nc-1 Pickup
1.00 A
0.20 sec
51Nc-1 Time Dial
Disk Emulation
Drop-out Characteristic
Normal Inverse
51Nc-1 IEC Curve
0.00 sec
Constant time adder
51Nc-1
NO
51Nc-1 ANSI Curve
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017