Prerequisites
A requirement for the use of trip circuit supervision is that the control voltage for the circuit breaker is at least
twice the voltage drop across the binary input (V
Since at least 19 V are needed for the binary input, the supervision can only be used with a system control
voltage of over 38 V.
2.12.2.1

Description

Supervision with Two Binary Inputs
When using two binary inputs, these are connected according to
contact on one side, and parallel to the circuit breaker auxiliary contacts on the other.
[prinzip-ausloesekreisueberwachung-2-binein-150502-kn, 1, en_US]
Figure 2-76
Supervision with two binary inputs not only detects interruptions in the trip circuit and loss of control voltage,
it also supervises the response of the circuit breaker using the position of the circuit breaker auxiliary contacts.
Depending on the conditions of the trip contact and the circuit breaker, the binary inputs are activated (logical
condition "H" in
In healthy trip circuits the condition that both binary inputs are not actuated ("L") is only possible during a
short transition period (trip contact is closed but the circuit breaker has not yet opened). A continuous state of
this condition is only possible when the trip circuit has been interrupted, a short-circuit exists in the trip circuit,
a loss of battery voltage occurs, or malfunctions occur with the circuit breaker mechanism. Therefore, it is
used as supervision criterion.
Table 2-15
No.
Trip contact
1
2
3
Closed
4
Closed
SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017
Principle of the trip circuit supervision with two binary inputs
Table
2-15), or not activated (logical condition "L").
Condition table for binary inputs, depending on RTC and CB position
Circuit breaker
Open
Closed
Open
Open
Closed
Open
> 2 · V
).
ct
BImin
Figure
2-76, parallel to the associated trip
52a Contact
52b Contact
Closed
Open
Closed
Open
Functions
2.12 Monitoring Functions
BI 1
Open
H
Closed
H
Open
L
Closed
L
BI 2
L
H
L
H
243