C.9 MEMOBUS/Modbus Data Table
 Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Digital Input Command
bit 0
bit 1
bit 2, 3
bit 4
0001H
bit 5
bit 6 to B
bit C
bit D
bit E
bit F
0002H
Frequency Reference
 Fault Trace Contents
The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2- and
U3- monitor parameters.
Fault Code
0002H
DC Bus Undervoltage (Uv1)
0003H
Control Power Supply Voltage Fault (Uv2)
0004H
Undervoltage 3 (Uv3)
0005H
Output Short-Circuit or IGBT Fault (SC)
0006H
Ground Fault (GF)
0007H
Overcurrent (oC)
0008H
Drive Overheat Warning (ov)
0009H
Heatsink Overheat (oH)
000AH
Overheat 1 (oH1)
000BH
Motor Overload (oL1)
000CH
Drive Overload (oL2)
000DH
Overtorque Detection 1 (oL3)
000EH
Overtorque Detection 2 (oL4)
000FH
Dynamic Braking Transistor (rr)
0010H
Braking Resistor Overheat (rH)
0011H
External Fault at input terminal S3 (EF3)
0012H
External Fault at input terminal S4 (EF4)
0013H
External Fault at input terminal S5 (EF5)
0014H
External Fault at input terminal S6 (EF6)
0015H
External Fault at input terminal S7 (EF7)
0016H
External Fault at input terminal S8 (EF8)
0017H
Internal Fan Fault (FAn)
0018H
Overspeed (oS)
0019H
Speed Deviation (dEv)
001AH
PG Disconnect (PGo)
001BH
Input Phase Loss (PF)
001CH
Output Phase Loss (LF)
001DH
Motor Overheat (PTC input) (oH3)
001EH
Digital Operator Connection (oPr)
001FH
EEPROM Write Error (Err)
0020H
Motor Overheat (PTC input) (oH4)
0021H
MEMOBUS/Modbus Communication Error (CE)
0022H
Option Communication Error (bUS)
0025H
Control fault (CF)
0026H
Zero-Serve Fault (SvE)
0027H
Option External Fault (EF0)
0028H
PID Feedback Loss (FbL)
568
Forward Run (0: Stop 1: Run)
Direction Command (0: Forward, 1: Reverse)
Reserved
External Fault
Fault Reset
Reserved
Multi-Function Digital Input S5
Multi-Function Digital Input S6
Multi-Function Digital Input S7
Multi-Function Digital Input S8
30000/100%
Table C.5 Fault Trace / History Register Contents
Fault Name
YASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual
Contents
Fault Code
009AH
Terminal board is not properly connected. (CPF25)
009BH
ASIC BB Circuit Error (CPF26)
009CH
ASIC PWM Setting Register Error (CPF27)
009DH
ASIC PWM Pattern Error (CPF28)
009EH
ASIC On-Delay Error (CPF29)
009FH
ASIC BBON Error (CPF30)
00A0H
ASIC Code Error (CPF31)
00A1H
ASIC Start-p Error (CPF32)
00A2H
Watch-dog Error (CPF33)
00A3H
ASIC Power/Clock Error (CPF34)
00A4H
External A/D Converter Error (CPF35)
00A9H
Control Circuit Error (CPF40)
00AAH
Control Circuit Error (CPF41)
00ABH
Control Circuit Error (CPF42)
00ACH
Control Circuit Error (CPF43)
00ADH
Control Circuit Error (CPF44)
00AEH
Control Circuit Error (CPF45)
0101H
Option compatibility error (oFA00)
0102H
Option not properly connected (oFA01)
0106H
A/D Conversion Error (oFA05)
0107H
Option Response Error (oFA06)
0111H
Option RAM Fault (oFA10)
0112H
Option Operation Mode Fault (SLMOD) (oFA11)
0113H
Drive Receive CRC Error (oFA12)
0114H
Drive Receive Frame Error (oFA13)
0115H
Drive Receive Abort Error (oFA14)
0116H
Option Receive CRC Error (oFA15)
0117H
Option Receive Frame Error (oFA16)
0118H
Option Receive Abort Error (oFA17)
0131H
Comm. ID Error (oFA30)
0132H
Model Code Error (oFA31)
0133H
Sumcheck Error (oFA32)
0134H
Comm. option timeout waiting for response (oFA33)
0135H
MEMOBUS Timeout (oFA34)
0136H
Drive timeout waiting for response (oFA35)
0137H
CI Check Error (oFA36)
0138H
Drive timeout waiting for response (oFA37)