B.10 o: Operator-Related Settings
B.10 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u

o1: Digital Operator Display Selection

No.
(Addr.
Name
Hex)
o1-01
Drive Mode Unit Monitor
(500)
Selection
o1-02
User Monitor Selection after
(501)
Power Up
o1-03
Digital Operator Display
(502)
Selection
o1-04
V/f Pattern Display Unit
(503)
o1-10
User-Set Display Units
(520)
Maximum Value
o1-11
User-Set Display Units
(521)
Decimal Display
<1> Default setting is dependent on parameter A1-02, Control Method Selection.
<2> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.
u

o2: Digital Operator Keypad Functions

No.
(Addr.
Name
Hex)
o2-01
LO/RE Key Function
(505)
Selection
o2-02
STOP Key Function
(506)
Selection
o2-03
User Parameter Default
(507)
Value
o2-04
Drive Model Selection
(508)
o2-05
Frequency Reference
(509)
Setting Method Selection
Operation Selection when
o2-06
Digital Operator is
(50A)
Disconnected
o2-07
Motor Direction at Power
(527)
Up when Using Operator
o2-09
(50D)
224
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: Uo-oo.
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
0: Hz
1: r/min
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Enter the drive model. Setting required only if installing a new control board. Default:
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using
the up and down arrow keys only.
0: The drive continues operating if the digital operator is disconnected.
1: An oPr fault is triggered and the motor coasts to stop.
0: Forward
1: Reverse
This parameter requires assigning drive operation to the digital operator.
Factory use.
YASKAWA ELECTRIC TOEP C710616 41B YASKAWA AC Drive - A1000 Quick Start Guide
Description
Description
Values
Page
Default: 106
(Monitor U1-06)
Range: 104 to 809
Default: 1
Range: 1 to 5
<1>
Default:
Range: 0 to 3
<1>
Default:
Range: 0, 1
<2>
Default:
Range: 1 to 60000
<2>
Default:
Range: 0 to 3
Values
Page
Default: 1
Range: 0, 1
Default: 1
Range: 0, 1
Default: 0
Range: 0 to 2
Determined by
drive capacity
Default: 0
Range: 0, 1
Default: 1
Range: 0, 1
Default: 0
Range: 0, 1