5.6 Wiring of Input and Output

Do not apply the voltage that exceeds the rated input voltage to the input terminal.
5.6.1
Input Wiring
Connection of photoelectric sensor and proximity sensor
Relay output type
Voltage output type
Precaution when using LED-equipped lead switch
Precaution when using two-wire type sensor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
NPN open collector output type
Two-wire output type
When a LED is connected in series to an input
contact such as LED-equipped lead switch, make
sure that the on voltage applied to the PLC input
terminal is greater than 21.6V DC. In particular,
take care when connecting a number of switches
in series.
If the input of PLC does not turn off because of
leakage current from the two-wire type sensor
"photoelectric sensor or proximity sensor", the use
of a bleeder resistor is recommended, as shown
below.
The formula is based on an input impedance of
5.6kΩ. The input impedance varies depending on
the input terminal number.