14.7
Generic communication function for Double Point
indication DPGAPC
14.7.1
Identification
Function description
Generic communication function for
Double Point indication
14.7.2
Functionality
Generic communication function for Double Point indication (DPGAPC) function block is used to
send double point position indications to other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It is especially intended to be used in
the interlocking station-wide logics.
14.7.3
Function block
IEC13000081 V1 EN-US
Figure 477: DPGAPC function block
14.7.4
Signals
Table 552: DPGAPC Input signals
Name
OPEN
CLOSE
VALID
Table 553: DPGAPC Output signals
Name
POSITION
Technical manual
IEC 61850
identification
DPGAPC
Type
Default
Description
BOOLEAN
0
Open indication
BOOLEAN
0
Close indication
BOOLEAN
0
Valid indication
Type
Description
INTEGER
Double point indication
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 14
Control
SEMOD55384-1 v4
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
SEMOD55850-5 v7
SEMOD54710-4 v5
SEMOD55883-1 v2
PID-4139-INPUTSIGNALS v12
PID-4139-OUTPUTSIGNALS v11
913