1MRK 502 066-UUS B
Table 736: VMMXU Non group settings (basic)
Name
Values (Range)
VAB_DbRepInt
1 - 300
Operation
Disabled
Enabled
VAB_ZeroDb
0 - 100000
VAB_Max
0.0 - 200.0
VAB_RepTyp
Cyclic
Dead band
Int deadband
GlobalBaseSel
1 - 12
VAB_AnDbRepInt
1 - 300
VBC_DbRepInt
1 - 300
VB_ZeroDb
0 - 100000
VBC_Max
0.0 - 200.0
VBC_RepTyp
Cyclic
Dead band
Int deadband
VBC_AnDbRepInt
1 - 300
VCA_DbRepInt
1 - 300
VC_ZeroDb
0 - 100000
VCA_Max
0.0 - 200.0
VCA_RepTyp
Cyclic
Dead band
Int deadband
VCA_AnDbRepInt
1 - 300
Table 737: VMMXU Non group settings (advanced)
Name
Values (Range)
VAB_HiHiLim
0.0 - 200.0
VAB_HiLim
0.0 - 200.0
VAB_LowLim
0.0 - 200.0
VAB_LowLowLim
0.0 - 200.0
VMagComp100
-10.000 - 10.000
VAB_Min
0.0 - 200.0
VAB_LimHys
0.000 - 100.000
Table continues on next page
Technical manual
Unit
Step
Default
Type
1
10
-
-
Disabled
m%
1
1
%VB
0.1
200.0
-
-
Cyclic
-
1
1
Type
1
10
Type
1
10
m%
1
1
%VB
0.1
200.0
-
-
Cyclic
Type
1
10
Type
1
10
m%
1
1
%VB
0.1
200.0
-
-
Cyclic
Type
1
10
Unit
Step
Default
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%
0.001
0.000
%VB
0.1
50.0
%
0.001
5.000
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Disbled/Enabled operation
Zero point clamping
Maximum value in % of VBase
Reporting type
Selection of one of the Global Base Value
groups
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
Maximum value in % of VBase
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping
Maximum value in % of VBase
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Description
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Magnitude factor to calibrate voltage at
100% of Vn
Minimum value in in % of VBase
Hysteresis value in % of range and is
common for all limits
Section 16
Monitoring
PID-3767-SETTINGS v5