ABB RELION 670 Series Technical Manual page 792

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
14.2.8.1
Identification
Function description
Interlocking for breaker-and-a-half
diameter
Interlocking for breaker-and-a-half
diameter
Interlocking for breaker-and-a-half
diameter
14.2.8.2
Functionality
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3), BH_LINE_B(3))
functions are used for lines connected to a breaker-and-a-half diameter according to figure 419.
BH_LINE_A
ANSI04000513 V1 EN-US
Figure 419: Switchyard layout breaker-and-a-half
Three types of interlocking modules per diameter are defined. BH_LINE_A (3) and BH_LINE_B (3)
are the connections from a line to a busbar. BH_CONN (3) is the connection between the two lines
of the diameter in the breaker-and-a-half switchyard layout.
786
IEC 61850
identification
BH_CONN
BH_LINE_A
BH_LINE_B
189
189G
152
289G
689
389G
6189
152
989
189G
989G
BH_CONN
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
3
-
3
-
3
289
189G
152
289G
689
389G
6289
989
289G
989G
1MRK 502 066-UUS B
GUID-03F1A3BB-4A1E-49E8-88C6-10B3876F64DA v4
WA1 (A)
WA2 (B)
BH_LINE_B
en04000513_ansi.vsd
Technical manual
M13570-3 v6
M13570-7 v4