Section 14
Control
Table 489: SCSWI Output signals
Name
EXE_OP
EXE_CL
SEL_OP
SEL_CL
SELECTED
RES_RQ
START_SY
CANC_SY
POSITION
OPENPOS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUSE
POS_INTR
XOUT
838
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
INTEGER
BOOLEAN
BOOLEAN
AU_OPEN and AU_CLOSE are used to issue automated commands as e.g. for load
shedding for opening respectively closing to the SCSWI function. They work
without regard to how the operator place selector, PSTO, is set. In order to have
effect on the outputs EXE_OP and EXE_CL, the corresponding enable input,
EN_OPEN respectively EN_CLOSE must be set, and that no interlocking is active.
L_SEL, L_OPEN and L_CLOSE are used for local command sequence connected to
binary inputs. In order to have effect, the operator place selector, PSTO, must be
set to local or to remote with no priority. If the control model used is Select before
operate, Also the corresponding enable input must be set, and no interlocking is
active. The L_SEL input must be set before L_OPEN or L_CLOSE is operated, if the
control model is Select before operate.
If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWI are used for a two-
or three-phase system, two or more of the inputs XPOSL1, XPOSL2 and XPOSL3 are
connected to the same source.
Description
Execute Open command
Execute Close command
Selected for open command
Selected for close command
Select conditions are fulfilled
Request signal to the reservation function
Starts the external synchronizing function
Cancels the external synchronizing function, started through
START_SY
Position indication
Open position indication
Closed position indication
The positions for poles A, B and C are not equal after a set time
Commands are blocked
Latest value of the error indication during command
Stopped in intermediate position
Execution information to XCBR/XSWI
1MRK 502 066-UUS B
PID-6500-OUTPUTSIGNALS v3
GUID-7DABB496-EABE-48A4-8078-7ED5D6D4FE14 v2
Technical manual