1MRK 502 066-UUS B
18.8.13.3
Function block
BLOCK
IEC10000285 V1 EN-US
Figure 605: I103GENCMD function block
18.8.13.4
Signals
Table 885: I103GENCMD Input signals
Name
BLOCK
Table 886: I103GENCMD Output signals
Name
CMD_OFF
CMD_ON
18.8.13.5
Settings
Table 887: I103GENCMD Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
PulseLength
0.000 - 60.000
InfNo
1 - 255
18.8.14
IED commands with position and select for IEC 60870-5-103
I103POSCMD
18.8.14.1
Functionality
I103POSCMD is a transceiver function that monitors activity on its input signals and interprets any
state transition into commands then sent over an established IEC 60870-5-103 link. Additionally, it
listens for general interrogation (GI) requests and replies to those with a GI response message
with the current state of each connected input.
Input POSITION is a double-indication signal, and it is GI enabled. This means that any state
transition, that is to ON, OFF, intermediate and faulty, is reported spontaneously. However, the
Technical manual
I103GENCMD
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd
Type
Default
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
-
s
-
Description
0
Block of command
Description
Command output OFF
Command output ON
Step
Default
1
1
0.001
0.400
1
1
Station communication
GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1
Description
Function type (1-255)
Pulse length
Information number for command output
(1-255)
GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v8
Section 18
PID-3970-INPUTSIGNALS v4
PID-3970-OUTPUTSIGNALS v4
PID-3970-SETTINGS v4
1179